One method of duct design relies on calculating the total effective length which is the sum of all the lengths of the straight sections of duct and the equivalent lengths of the fittings.
Hvac duct fittings equivalent length chart.
1 psi equals 27 7 inches of water gauge.
Each fitting has an effective length that equates its pressure drop to an equivalent amount of straight duct.
Fittings such as elbows tees and valves represent a significant component of the pressure loss in most pipe systems.
12 x 7 flat oval 1000 cfm solution.
From table a 3 the equivalent round size is 9 4 inches.
When you add up the effective lengths of all the fittings and then add that number to the length of the straight sections in the most restrictive runs in the return and supply ducts you find the total effective length tel.
The weakness of the equivalent length method is that.
Energy vanguard this duct design shows the layout of a duct system including the fittings and duct sizes.
Ordinary heating ventilating and air conditioning duct systems read air pressures at 0 4 psi or less often much less.
Equivalent duct sizes for same friction loss from.
Use the friction chart at 1000 cfm in 9 4 inch diameter to friction loss is 0 5 in water 100 ft.
The strength of the equivalent length method is that it is very simple to calculate.
The sum of all equivalent lengths of fittings used and the measured distances of all pipe and duct from room terminal to the air handler should be calculated for each.